Electromagnetic flowmeter Picomag DMA
Brand: Endress+HauserElectromagnetic flowmeter Picomag DMA
Brand: Endress+Hauser
Fundamental Specs at a Glance
Electrodes: 1.4404/316L
Permissible short-term temperature, maximum one hour:
85 °C (185 °F)
Repetition after 4 hours at the earliest
Field of application
Picomag is a compact electromagnetic flowmeter that simultaneously measures flow, temperature and conductivity. The device is suited for applications in secondary circuits with conductive liquids, and the bidirectional measuring principle is virtually independent of pressure, density, temperature and viscosity. Wireless connection to the SmartBlue app over Bluetooth® ensures fast and easy plug-and-play commissioning , operation and maintenance.
Depending on the chosen diameter, the maximum flow rate is 35 l/min (DMA15, DN15), 75 l/min (DMA20, DN20), 150 l/min (DMA25, DN25) or 750 l/min (DMA50, DN50). Conductivities from 20 to 10 000 μS/cm (DMA50) or up to 30 000 μS/cm (DMA15, DMA20, DMA25) can be measured. The temperature measurement range is -10 to 70 °C independent of the diameter.
Key Benefits
- Three measurements in one device: volume flow, temperature, conductivity
- Intuitive configuration and operation as well as easy access via SmartBlue app, ideal for measuring points that are difficult to access
- Large user-friendly and auto-rotatable display for local process control
- Plug-and-play thanks to IO-Link for easy integration into all fieldbus systems
- Compact size enables installation in tight spaces like skids
Specifications
Brand
Field of Application
- Heating & Cooling
Industry
- Other industries
Target Customer
- Food & beverage industry
- Power & Energy industry
- Semiconductor industry
- Automative and transportation industry
Liquids
Product headline
- Smart magmeter for utilities – intuitive · convenient · multivariable.
- Time-saving, easy configuration even in places difficult to reach – secure Bluetooth connection.
- Ideal for process quality control and monitoring due to temperature and conductivity measurement in utilities.
Sensor features
- Fewer measuring points necessary – simultaneous flow, conductivity and temperature measurement. Cost-efficient specialist for use in tight spaces e.g. skids – sensor and transmitter in one housing.
- High shock and vibration resistance. Degree of protection: IP65/67. Empty pipe detection.
Transmitter features
- Quick offline configuration check – unique, comfortable knock functionality. Simple device access through its whole lifecycle – no manual needed due to intuitive SmartBlue app. Effortless configuration of several devices – settings can be saved and loaded into other meters. Flexible integration into all fieldbus systems – plug-and-play device with IO-Link.
- Wireless remote access via Bluetooth SmartBlue app. IO-Link and various I/Os for all line-sizes. 1.4" TFT color display with backlight.
Nominal diameter range
- DN15 to 50 (1/2 to 2")
Wetted materials
- PEEK, Stainless Steel, FKM, EPDM
- Electrodes: 1.4404/316L
Measured variables
- Volume flow, Temperature, Conductivity
Max. measurement error
- Volume flow: +/-0.8% o.r. +/- 0.1% o.f.s
Measuring range
- up to 750 l/min
Max. process pressure
- 16 bar
Medium temperature range
- -10 to 70°C (+14 to +158 °F)
- Permissible short-term temperature, maximum one hour:
- 85 °C (185 °F)
- Repetition after 4 hours at the earliest
Ambient temperature range
- -10 to 60 °C
Sensor housing material
- 1.4404/316L, Polycarbonate
Transmitter housing material
- 1.4404/316L, Polycarbonate
Degree of protection
- IP 65/67
Display/Operation
- Integrated display, operation via Bluetooth technology
Outputs
- Current (4 to 20mA)
- Pulse
- Switch
- Voltage (2 to 10V)
Inputs
- Status
Digital communication
- IO-Link
Power supply
- 18 to 30V DC
Product safety
- cULus listing
Hygienic approvals and certificates
- Drinking water approvals: NSF